For Siemens PLC 1200

​6ES7214-1BE30-0XB0
SIMATIC S7-1200, CPU 1214C, compact CPU, AC/DC/relay, onboard I/O: 14 DI 24 V DC; 10 DO relay 2 A; 2 AI 0-10 V DC, Power supply: AC 85-264 V AC at 47-63 Hz, Program/data memory 50 KB
Chat Now

Product Details

Product Description

6ES7214-1BE30-0XB0

SIMATIC S7-1200, CPU 1214C, compact CPU, AC/DC/relay, onboard I/O: 14 DI 24 V DC; 10 DO relay 2 A; 2 AI 0-10 V DC, Power supply: AC 85-264 V AC at 47-63 Hz, Program/data memory 50 KB

Brand Name

Siemens

Model Number

6ES7214-1BE30-0XB0

Net Weight (kg)

0,478 Kg

Place of Origin

Germany

Lead Time

In Stock

Packaging Dimension

11,40 x 11,80 x 8,60

Delivery Time

2-3 days

Specifications

 14 DI 24 V DC


Detailed Images

image001


We're not just sellers, we also have professional skills

General information

Product type designation CPU 1214C AC/DC/relay

Engineering with

● Programming package STEP 7 V10.5 or higher

Supply voltage

Rated value (AC)

● 120 V AC Yes

● 230 V AC Yes

permissible range, lower limit (AC) 85 V

permissible range, upper limit (AC) 264 V

Line frequency

● permissible range, lower limit 47 Hz

● permissible range, upper limit 63 Hz

Load voltage L+

● Rated value (DC) 24 V

● permissible range, lower limit (DC) 5 V

● permissible range, upper limit (DC) 250 V

Input current

Current consumption (rated value) 100 mA at 120 V AC; 50 mA at 240 V AC

Current consumption, max. 300 mA at 120 V AC; 150 mA at 240 V AC

Inrush current, max. 20 A; at 264 V

Output current

for backplane bus (5 V DC), max. 1 600 mA; Max. 5 V DC for SM and CM

Encoder supply

24 V encoder supply

● 24 V Permissible range: 20.4V to 28.8V

Power loss

Power loss, typ. 14 W

Memory

Work memory

● integrated 50 kbyte

● expandable No

Load memory

● integrated 2 Mbyte

● Plug-in (SIMATIC Memory Card), max. 24 Mbyte; with SIMATIC memory card

Backup

● present Yes; Entire project maintenance-free in the integral EEPROM

● without battery Yes

CPU processing times

for bit operations, typ. 0.1 µs; / Operation

for word operations, typ. 12 µs; / Operation

for floating point arithmetic, typ. 18 µs; / Operation

CPU-blocks

Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of

addressable blocks ranges from 1 to 65535. There is no

restriction, the entire working memory can be used

OB

● Number, max. Limited only by RAM for code

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags),

max.

2 048 byte

Flag

● Number, max. 8 kbyte; Size of bit memory address area

Address area

I/O address area

● Inputs 1 024 byte

● Outputs 1 024 byte

Process image

● Inputs, adjustable 1 kbyte

● Outputs, adjustable 1 kbyte

Hardware configuration

Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules

Time of day

Clock

● Hardware clock (real-time) Yes

● Backup time 240 h; Typical

● Deviation per day, max. ±60 s/month at 25 °C

Digital inputs

Number of digital inputs 14; Integrated

● of which inputs usable for technological

functions

6; HSC (High Speed Counting)

Source/sink input Yes

Input voltage

● Rated value (DC) 24 V

● for signal "0" 5 V DC at 1 mA

● for signal "1" 15 V DC at 2.5 mA

Input current

● for signal "1", typ. 1 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,

selectable in groups of four

— at "0" to "1", min. 0.2 ms

— at "0" to "1", max. 12.8 ms

for interrupt inputs

— parameterizable Yes

for technological functions

— parameterizable Single phase: 3 at 100 kHz & 1 at 30 kHz, differential: 3 at 80 kHz

& 1 at 30 kHz

Cable length

● shielded, max. 500 m; 50 m for technological functions

● unshielded, max. 300 m; For technological functions: No

Digital outputs

Number of digital outputs 10; Relays

Short-circuit protection No; to be provided externally

Switching capacity of the outputs

● with resistive load, max. 2 A

● on lamp load, max. 30 W with DC, 200 W with AC

Output delay with resistive load

● "0" to "1", max. 10 ms; max.

● "1" to "0", max. 10 ms; max.

Switching frequency

● of the pulse outputs, with resistive load, max. 1 Hz

Relay outputs

● Number of relay outputs 10

● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Analog inputs

Number of analog inputs 2

Input ranges

● Voltage Yes

Input ranges (rated values), voltages

● 0 to +10 V Yes

● Input resistance (0 to 10 V) ≥100k ohms

Cable length

● shielded, max. 100 m; twisted and shielded

Analog outputs

Number of analog outputs 0

Cable length

● shielded, max. 100 m; shielded, twisted pair

Analog value generation for the inputs

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign),

max.

10 bit

● Integration time, parameterizable Yes

● Conversion time (per channel) 625 µs

Encoder

Connectable encoders

● 2-wire sensor Yes

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● min. 0 °C

● max. 55 °C

● horizontal installation, min. 0 °C

● horizontal installation, max. 55 °C

● vertical installation, min. 0 °C

● vertical installation, max. 45 °C

● permissible temperature change 5°C to 55°C, 3°C / minute

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Operation, min. 795 hPa

● Operation, max. 1 080 hPa

● Storage/transport, min. 660 hPa

● Storage/transport, max. 1 080 hPa

Altitude during operation relating to sea level

● Installation altitude, min. -1 000 m

● Installation altitude, max. 2 000 m

Relative humidity

● Operation, max. 95 %; no condensation

Vibrations

● Vibration resistance during operation acc. to

IEC 60068-2-6

2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail

● Operation, tested according to IEC 60068-2-6 Yes

Shock testing

● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak

value), duration 11 ms

Pollutant concentrations

● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

Dimensions

Width 110 mm

Height 100 mm

Depth 75 mm

Weights

Weight, approx. 455 g