FX1S-14MR-ES/UL parameter Description

- Apr 20, 2019-

"FX1S-14MR-ES/UL Power supply Specification"

 Rated Voltage: AC100~240V

 Voltage allowable range: A085~264V

 Rated Frequency: 50/60HZ

 Allowed transient time: less than 10ms

 Power fuse: 250V 1 A 5Ф*20mm

    Impact Current:                                           

    Up to 15A 5ms below/AC100V                                            

 Up to 25A 5ms below/AC200V

 Power Consumption (W) (Input current portion (7mA/1 point, 5mA/1 Point) is 


also included): 19W


Sensor power supply: DC24V 400mA

 "FX1S-14MR-ES/UL Input Specifications"

 Input points: 8

 Input connection method: Terminal table (M3 screws)

 Input form: leakage/Source Type

 Input signal voltage: DC24V±10%

 Input signal Current: 7mA/DC24V

 Input on current: 4.5mA or more

 Input off current: less than 1.5mA

 Input resistor: 3.3KΩ (X010 after 4.3KΩ)

    Input response Time:

    Approx. 10ms

 X000~X017 can pass through the built-in digital filter D8020 change 


history to 0~15ms; In the case of 0, X000,X001 is 10μs,x002~ X017 as 


50μs.

                 Input signal form: no voltage contact input

                 NPN Open Set Electrode transistor

 PNP Open collector transistor

 Circuit Insulation: Optocoupler insulation

Input action representation: LED light on when input on

 "FX1S-14MR-ES/UL Relay Output Specifications"

 Output points: 6

 Output connection mode: Terminal table (M3 screws)

 Output Type: Relays

 External power supply: AC250V DC30V below

 Circuit Insulation: Mechanical insulation

 Motion representation: The LED light is on when the relay coil is powered 


on

 Maximum resistance load: 2A/1 point, 8A/1 COM terminal

 Maximum inductive load: 80VA

 Minimum load: DC5V 2mA

     Response time: approx. 10ms FX1S-14MR-ES/UL Dimensions: 60*75*90